悬挑板施工方案 - 图文

景裕豪园三期14、15栋悬挑板施工方案 小梁截面抵抗矩W(cm) 小梁截面惯性矩I(cm) 4383.33 416.67 小梁弹性模量E(N/mm) 小梁计算方式 29350 二等跨连续梁 q1=0.9×max[1.2(G1k+ (G2k+G3k)×h)+1.4Q1k,1.35(G1k

+(G2k+G3k)×h)+1.4×0.7×Q1k]×b=0.9×max[1.2×(0.3+(24+1.1)×0.12)+1.4×2.5,1.35×(0.3+(24+1.1)×0.12)+1.4×0.7×2.5]×0.3=2.018kN/m

因此,q1静=0.9×1.2×(G1k +(G2k+G3k)×h)×b=0.9×1.2×(0.3+(24+1.1)×0.12)×0.3=1.073kN/m q1活=0.9×1.4×Q1k×b=0.9×1.4×2.5×0.3=0.945kN/m q2=0.9×1.2×G1k×b=0.9×1.2×0.3×0.3=0.097kN/m p=0.9×1.4×Q1k=0.9×1.4×2.5=3.15kN 计算简图如下:

1、强度验算

M1=0.125q1静L2+0.125q1活L2=0.125×1.073×0.92+0.125×0.945×0.92=0.204kN·m

M2=max[0.07q2L2+0.203pL,0.125q2L2+0.188pL]=max[0.07×0.097×0.92+0.203×3.15×0.9,0.125×0.097×0.92+0.188×3.15×0.9]=0.581kN·m

M3=max[q1L12/2,q2L12/2+pL1]=max[2.018×0.252/2,0.097×0.252/2+3.15×0.25]=0.791kN·m

48

景裕豪园三期14、15栋悬挑板施工方案 Mmax=max[M1,M2,M3]=max[0.204,0.581,0.791]=0.791kN·m σ=Mmax/W=0.791×106/83330=9.487N/mm2≤[f]=15.444N/mm2 满足要求! 2、抗剪验算

V1=0.625q1静L+0.625q1活L=0.625×1.073×0.9+0.625×0.945×0.9=1.135kN V2=0.625q2L+0.688p=0.625×0.097×0.9+0.688×3.15=2.222kN V3=max[q1L1,q2L1+p]=max[2.018×0.25,0.097×0.25+3.15]=3.174kN Vmax=max[V1,V2,V3]=max[1.135,2.222,3.174]=3.174kN

τmax=3Vmax/(2bh0)=3×3.174×1000/(2×50×100)=0.952N/mm2≤[τ]=1.782N/mm2 满足要求! 3、挠度验算

q=(γG(G1k +(G2k+G3k)×h))×b=(1×(0.3+(24+1.1)×0.12))×0.3=0.994kN/m

挠度,跨中νmax=0.521qL4/(100EI)=0.521×0.994×9004/(100×9350×416.67×104)=0.087mm≤[ν]=L/250=900/250=3.6mm;

悬臂端νmax=ql14/(8EI)=0.994×2504/(8×9350×416.67×104)=0.012mm≤[ν]=2×l1/250=2×250/250=2mm 满足要求!

六、主梁验算

主梁类型 主梁计算截面类型(mm) 主梁抗剪强度设计值[τ](N/mm) 主梁弹性模量E(N/mm) 主梁计算方式 22钢管 Ф48×3 125 206000 三等跨连续梁 主梁截面类型(mm) 主梁抗弯强度设计值[f](N/mm) 主梁截面抵抗矩W(cm) 主梁截面惯性矩I(cm) 可调托座内主梁根数 432Φ48×3.5 205 4.49 10.78 1 1、小梁最大支座反力计算 q1=0.9×max[1.2(G1k

+(G2k+G3k)×h)+1.4Q1k,1.35(G1k

+(G2k+G3k)×h)+1.4×0.7×Q1k]×b=0.9×max[1.2×(0.5+(24+1.1)×0.12)+1.4×1.5,1.35×(0.5+(24+1.

49

联系客服:779662525#qq.com(#替换为@)