水电站短路电流计算 下载本文

1S时:If G110,1?2.13?175/0.85?16.094KA;

3?15.75175/0.85?17.303KA;

3?15.75175/0.85?18.739KA;

3?15.752S时:If G110,2?2.29?4S时:If G110,4?2.48?连接2200kV系统发电机送至d2点的短路电流: 0S时:If G220,0?2.50?2?175/0.85?37.780KA;

3?15.752?175/0.85?31.433KA;

3?15.752?175/0.85?30.980KA;

3?15.750.1S时:If G220,0.1?2.08?0.2S时:If G220,0.2?2.05?1S时:If G110,1?2.21?2?175/0.85?33.398KA;

3?15.752?175/0.85?35.513KA;

3?15.752?175/0.85?37.780KA;

3?15.752S时:If G220,2?2.35?4S时:If G220,0?2.50?3、短路点d3

0.0710.1100.655100.6508.7300.214d30.214

合并串并联支路

0.0710.1100.6550.4328.7300.21410.864d3 (3)、转移电抗计算

①、110kV系统对短路点d3的转移电抗:

XS110f?0.110?1?0.655?8.730?10.495;

②、220kV系统对短路点d3的转移电抗:

XS220f?0.071?0.655?8.730?9.456;

③、连接在110kV母线上的发电机组对短路点d3的转移电抗:

XG110f?0.864?1?0.655?8.730?11.249;

④、连接在220kV母线上的2台发电机组对短路点d3的转移电抗:

XG220f?0.432?0.655?8.730?9.817;

⑤、短路点d3连接发电机组对短路点d3的转移电抗:

XGf?0.214?8.730?8.944;

(2)计算电抗:

220kV系统和110kV系统较发电机可以看做无穷大功率电源处理,直接计算其对的短路点d3电流;

①、连接在110kV母线上的发电机组对短路点d3的计算电抗:

XG110js?11.249?175/0.85?2.316;

1000②、连接在220kV母线上的3台发电机组对短路点d3的计算电抗:

XG220js?9.817?2?175/0.85?4.0423?3;

1000③、短路点d3连接发电机组对短路点d3的计算电抗:

XGjs?8.944?175/0.85?1.8414;

1000(7)短路电流标幺值

①、110kV系统对短路点d3的短路电流:

Is110??1?0.0953;

10.4951?0.1058; 9.4561?0.1019 9.817②、200kV系统对短路点d3的短路电流:

Is220??③连接在220kV母线上的发电机组对短路点d3的短路电流:

Is220??④、连接在110kV母线上的发电机组对短路点d3的短路电流:

查《电力工程电气设计手册·电气一次》手册第138页Xjs?2.316可知:

IG220,0?0.45;IG220,0.1?0.45;IG220,0.2?0.46;IG220,1?0.46;IG220,2?0.46;IG220,4?0.46;⑤、短路点d3连接发电机组对短路点d3的短路电流:

查《电力工程电气设计手册·电气一次》手册第138页Xjs?1.8414可知:

IG220,0?0.56;IG220,0.1?0.56;IG220,0.2?0.58;IG220,1?0.59;IG220,2?0.59;IG220,4?0.59;

(8)短路电流有名值 电流基准值:IB?SB1000??55.051KA; 3UB3?10.5短路点d3时110kV系统送至的短路点d3电流:

IfS110?0.0953?55.051?5.246;

短路点d3时220kV系统送至的短路点d3电流:

IfS220?0.1058?55.051?5.824;

连接在220kV母线上的发电机组对短路点d3的短路电流:

IfS?0.1019?55.051?5.610;

连接110kV系统发电机送至d3点的短路电流: 0S时:If G110,0?0.45?175/0.85?1.530KA; 3?37175/0.85?1.530KA; 3?37175/0.85?1.480KA; 3?370.1S时:If G110,0.1?0.45?0.2S时:If G110,0.2?0.46?