欧姆龙NS高功能触摸屏常见使用问题 下载本文

1.NS怎么重装及升级系统程序? ............................................................................................ 2 2.NS屏幕右下角一直显示“Connecting”,画面不显示? ................................................ 2 3.NT的画面怎么转换成NS的画面? ...................................................................................... 2 4.NS内部控件可以调用自己的图片吗? ................................................................................ 2 5.NS怎么显示负数? .................................................................................................................. 2 6.NS怎么显示小数点? .............................................................................................................. 3 7.NS怎么显示浮点数据? ........................................................................................................ 4 8.NS控件(触摸按键、数字输入等)设置操作权限? ........................................................ 5 9.NS下载完画面程序后,如何在屏上直接查看画面程序? ................................................ 6 10.如何通过PLC来切换NS画面? ......................................................................................... 6 11.NS的画面如何实现多国语言切换功能? .......................................................................... 6 12.NS如何设置屏幕保护功能? .............................................................................................. 8 13.在CX-Designer软件的通信设置中,没有Hostlink协议选项? ................................. 9 14.NS使用标签功能对象中字符串间接参考的功能时,显示中文字符出现乱码? .......... 9 15.NS如何禁止修改系统菜单? ............................................................................................ 10 16.如何使用CX-Designer软件转换画面程序的系统版本? ............................................. 11 17.NS与CPM2AH通信,NS上显示“MRES=11,SRES=03”的错误? ................................. 11 18 触摸屏和PLC上电连接后程序画面不显示,如何处理? ............................................... 11 19. 触摸屏上电和计算机连接后无法下载画面程序,如何处理? ..................................... 12 20.触摸屏如何安装系统程序? ............................................................................................. 12 21.触摸屏显示和PLC内数据不符合,如何处理? ............................................................. 13 22.NS动画功能如何实现? .................................................................................................... 14 23.为什么做的中文画面后,下传到NT31/631(C)后中文都是乱码 .................................. 14 23.NT系列触摸屏进入不了系统传输画面 .............................................................................. 15 24. NT系列与PLC连接后,一上电显示初始画面后一闪就黑屏了 .................................... 15 25.NT31/NT631系列在上下载画面时注意事项? ................................................................ 15 26.如何安装系统程序? ......................................................................................................... 15 27.NT31(C)/631(C)触摸屏上显示“system initializing”? ............................... 16 28.NT31/NT631怎么设置密码? ............................................................................................ 16 29.NT631C 画面中使用到HR区时,下载画面时报HR地址错误? ................................... 16 30.NT31C-ST141-V2下载画面时,软件中“提示控制/通知区域的设定不合适,是否要现在就设置”? ......................................................................................................................... 16 31.如何刷新NT31/631C-EV3的 2.1G中文系统? .............................................................. 16 32.NT31C进入传送模式时,出现“数据画面被破坏”提示? .......................................... 17 33. NT31/631C为什么一上电显示选择英文/日文界面? ...................................................... 18 34.NT31/631电池没电画面会丢吗? .................................................................................... 18 35.NT31/631和CP1H通讯,触摸屏上按钮地址使用同一通道的两个位,例0.00/0.01,此时置位0.00,然后再置位0.01时,0.00就会被复位? ................................................. 18 36.NT31/631(C)把画面从屏中上载上来出现乱码? ........................................................... 18 37.NT怎么显示负数? ............................................................................................................ 19 38.NT画面转换NS画面时,转换失败? ................................................................................ 20

- 1 -

1.NS怎么重装及升级系统程序?

需要使用CF卡,把编程Designer软件对应的安装目录:

C:\\Program Files\\OMRON\\CX-One\\CX-Designer\\RecoverUpdate_6_6下的所有文件拷贝到CF卡内,NS断电插入CF卡,然后NS上电,NS会自动读取,选择升级覆盖系统即可。

2.NS屏幕右下角一直显示“Connecting”,画面不显示? 这个原因是由于NS与PLC没有通信成功,导致的原因如下: ①电缆损坏、接线不正确,请检查接线。

②NS、PLC端口设置的波特率不一致,需要设成一致。 ③PLC与NS使用的协议(HOSTLINK、NTLINK)不一致。

3.NT的画面怎么转换成NS的画面?

安装NS编辑软件时自动会安装NT31C_631C Conversion Support Tool这个文件转换工具,支持把NT31C_631C-V2版本的NT画面数据转换成NS画面程序。

4.NS内部控件可以调用自己的图片吗?

可以的,图片格式支持BMP、JPEG格式,把自己的图片拷贝到编辑软件的安装目录下的BMPfiles文件夹。C:\\Program Files\\OMRON\\CX-One\\CX-Designer\\intaparts\\BMPfiles 用三芯的XW2Z-200S-V这根电缆只能传画面无法传送系统程序,而XW2Z-200S-CV的这根电缆既可以传画面也能传系统程序。

5.NS怎么显示负数?

实际PLC内存值 F123 F000 0123 8123 8000 0123

数据格式 BCD1(singed(leftmost digit:F 1 WORD) BCD1(singed(leftmost digit:F 2 WORD) BCD2(singed(leftmost digit:1 1 WORD) BCD2(singed(leftmost digit:1 2 WORD) 实际显示 -123 - 2 -

6.NS怎么显示小数点?

① Format:设置整数位、小数位 ② Set Unit&Scale设定标定 例:

数据格式 BCD INT(Signed ) INT(Unsigned )

输入 12.34 Format 设定2个整数位,2个小数 SUnit&Scale 设定标定Scale为0.01 实际PLC内存的值 1234 4D2 4D2 注:4D2就1234的16进制值 - 3 -

7.NS怎么显示浮点数据?

目前NS系列可以支持浮点数据(32位单精度浮点)。 ① Display:选择十进制(Decimal) ② Storage:选择浮点(Real) ③ Format:选择整数与小数的位数